this post was submitted on 09 Aug 2024
5 points (100.0% liked)
homelab
6585 readers
5 users here now
founded 4 years ago
MODERATORS
you are viewing a single comment's thread
view the rest of the comments
view the rest of the comments
Looking at the diagram, I don't see any issue with the network topology. And the power arrangement also shouldn't be a problem, unless you require the camera/DVR setup to persist during a power cut.
In that scenario, you would have to provide UPS power to all of: the PoE switch, the L3 switch, and the NVR. But if you don't have such a requirement, then I don't see a problem here.
Also, I hope you're doing well now.